EasyManuals Logo

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 User Manual

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
Configuration
4.9 Data points
CP 1243-1
Operating Instructions, 12/2016, C79000-G8976-C365-02
79
Buffered transfer - Conditionally spontaneous
The value is transferred only when one of the following conditions is fulfilled:
The communications partner queries the station.
The value of another event with the transmission mode “Spontaneous" is transferred.
4.9.9
Threshold value trigger
Note
Threshold value trigger: Calculation only after "Analog value preprocessing"
Note that the analog value preprocessing is performed before the check for a configured
threshold value and before calculating the threshold value.
This affects the value that is configured for the threshold value trigger.
Note
No Threshold value trigger if Mean value generation is configured
If mean value generation is configured, no threshold value trigger can be configured for the
analog value event involved.
For the time sequence of the analog value preprocessing refer to the section Analog value
preprocessing (Page 81).
Threshold value trigger
Function
If the process value deviates by the amount of the threshold value, the process value is
saved.
Two methods are used to calculate the threshold value deviation:
Absolute method
With binary and counter values as well as with analog values with configured mean value
generation, the absolute method is used to calculate the threshold value deviation.
Integrative method
With analog values without configured mean value generation, the integrating method is
used to calculate the threshold value deviation.
In the integration threshold value calculation, it is not the absolute value of the deviation
of the process value from the last stored value that is evaluated but rather the integrated
deviation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 and is the answer not in the manual?

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 Specifications

General IconGeneral
Compatible ControllersS7-1200
InterfaceEthernet
Power Supply24 V DC
Number of Possible Connections8
Mounting TypeDIN rail
Weight200 g
Data Transfer Rate10/100 Mbps
ProtocolsTCP/IP, UDP, DNP3, IEC 60870-5-104
Supply Voltage20.4 ... 28.8 V DC
Current Consumption100 mA
Operating Temperature-20 ... +60 °C

Related product manuals