EasyManuals Logo

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 User Manual

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
Configuration
4.9 Data points
CP 1243-1
80 Operating Instructions, 12/2016, C79000-G8976-C365-02
Absolute method
For each binary value a check is made to determine whether the current (possibly smoothed)
value is outside the threshold value band. The current threshold value band results from the
last saved value and the amount of the configured threshold value:
Upper limit of the threshold value band: Last saved value + threshold value
Lower limit of the threshold value band: Last saved value - threshold value
As soon as the process value reaches the upper or lower limit of the threshold value band,
the value is saved. The newly saved value serves as the basis for calculating the new
threshold value band.
Integrative method
The integration threshold value calculation works with a cyclic comparison of the integrated
current value with the last stored value. The calculation cycle in which the two values are
compared is 500 milliseconds.
(Note: The calculation cycle must not be confused with the scan cycle of the CPU memory
areas).
The deviations of the current process value are totaled in each calculation cycle. The trigger
is set only when the totaled value reaches the configured value of the threshold value trigger
and a new process value is entered in the send buffer.
The method is explained based on the following example in which a threshold value of 2.0 is
configured.
Table 4- 3 Example of the integration calculation of a threshold value configured with 2.0
Time [s]
(calculation cycle)
Process value
stored in the
send buffer
Current process
value
Absolute deviation
from the stored
value
Integrated devia-
tion
0
20.0
20.0
0
0
0.5 20.3 +0.3 0.3
1.0
19.8
-0.2
0.1
1.5
20.2
+0.2
0.3
2.0
20.5
+0.5
0.8
2.5
20.3
+0.3
1.1
3.0
20.4
+0.4
1.5
3.5
20.5
20.5
+0.5
2.0
4.0
20.4
-0.1
-0.1
4.5
20.1
-0.4
-0.5
5.0
19.9
-0.6
-1.1
5.5
20.1
-0.4
-1.5
6.0
19.9
19.9
-0.6
-2.1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 and is the answer not in the manual?

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 Specifications

General IconGeneral
Compatible ControllersS7-1200
InterfaceEthernet
Power Supply24 V DC
Number of Possible Connections8
Mounting TypeDIN rail
Weight200 g
Data Transfer Rate10/100 Mbps
ProtocolsTCP/IP, UDP, DNP3, IEC 60870-5-104
Supply Voltage20.4 ... 28.8 V DC
Current Consumption100 mA
Operating Temperature-20 ... +60 °C

Related product manuals