Configuration
4.10 Messages
CP 1243-1
Operating Instructions, 12/2016, C79000-G8976-C365-02
89
Requirements and necessary information
Remember the following requirements in the CP configuration for the transfer of e-mails:
Enabling telecontrol communication ("Communication types") parameter group
Configuring the "E-mail configuration" parameter group (see "Security" parameter group)
To do this, you require the following information:
Access data of the SMTP server: Address, port number, user name, password
CP's own e-mail address
Email address of the recipient
"Message parameter"
Here you configure the recipient, the subject and the text of the message.
"Trigger"
In the "Trigger" parameter group you configure triggering for sending the message and other
parameters.
E-mail trigger
Specifies the event for which the sending of the e-mail is triggered.
Use PLC tag
For the trigger signal to send the e-mail, the edge change (0 → 1) of the trigger bit
"PLC tag for trigger" is evaluated that is set by the user program. When necessary, a
separate trigger bit can be configured for each e-mail. For information on the trigger
bit, see below.
CPU changes to STOP
CPU changes to RUN
Connection to a partner interrupted
Triggers the sending of the e-mail when the connection to a partner is interrupted.
Connection to a partner established
Triggers the sending of the e-mail when the connection returns.
Connection establishment to partner failed
Triggers the sending of the e-mail when the connection to a partner could not be
established.
Teleservice session started
Teleservice session ended
PLC tag for trigger
PLC tag for the e-mail trigger "Use PLC tag"
If the memory area of the trigger bit is in the bit memory or in a data block, the trigger bit
is reset to zero when the e-mail is sent.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 and is the answer not in the manual?

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 Specifications

General IconGeneral
Compatible ControllersS7-1200
InterfaceEthernet
Power Supply24 V DC
Number of Possible Connections8
Mounting TypeDIN rail
Weight200 g
Data Transfer Rate10/100 Mbps
ProtocolsTCP/IP, UDP, DNP3, IEC 60870-5-104
Supply Voltage20.4 ... 28.8 V DC
Current Consumption100 mA
Operating Temperature-20 ... +60 °C

Related product manuals