Configuration
4.8 Security
CP 1243-1
Operating Instructions, 12/2016, C79000-G8976-C365-02
57
Assigning certificates locally
To be able to use an imported certificate for the CP, you need to specify it in the "Security"
parameter group of the CP. Follow the steps outlined below:
1. In the STEP 7 project select the CP.
2. Navigate to the parameter group "Security > Certificate manager".
3. In the table, double-click on the cell with the entry "<Add new>".
The "Certificate manager" table of the Global security settings is displayed.
4. In the table. select the required third-party certificate and to adopt it click the green check
mark below the table.
The selected certificate is displayed in the local table of the CP.
Only now will the third-party certificate be used for the CP.
Exporting certificates for applications of third-party vendors (e.g. logging server)
For communication with applications of third-party vendors, the third-party application
generally also requires the certificate of the CP.
You export the certificate of the CP for communications partners from third-party vendors in
much the same way as when importing (see above). Follow the steps outlined below:
1. In the STEP 7 project open the global certificate manager:
Global security settings > Certificate manager
2. Open the "Device certificates" tab.
3. In the table select the row with the required certificate and select the shortcut menu
"Export".
4. Save the certificate in the file system of the PC of the connected engineering station.
Now you can transfer the exported certificate of the CP to the system of the third-party
vendor.
Certificate for logging server
If you use a logging server in your system, export the SSL certificate for the authentication of
the CP on the server.
Change certificate: Subject Alternative Name
STEP 7 adopts the properties "DNS name", "IP address", and "URI" from the parameter
"Subject Alternative Name" (Windows: "Alternative applicant name") from the STEP 7
configuration data.
You can change this parameter of a certificate inn the certificate manager of the global
security settings. To do this, select the a certificate in the table of device certificates and call
the shortcut menu "Renew". Properties of the parameter "Alternative name of the certificate
owner" changed in STEP 7 are not adopted by the STEP 7 project.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 and is the answer not in the manual?

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 Specifications

General IconGeneral
Compatible ControllersS7-1200
InterfaceEthernet
Power Supply24 V DC
Number of Possible Connections8
Mounting TypeDIN rail
Weight200 g
Data Transfer Rate10/100 Mbps
ProtocolsTCP/IP, UDP, DNP3, IEC 60870-5-104
Supply Voltage20.4 ... 28.8 V DC
Current Consumption100 mA
Operating Temperature-20 ... +60 °C