Diagnostics and upkeep
5.4 SNMP
CP 1243-1
Operating Instructions, 12/2016, C79000-G8976-C365-02
95
Range of performance of the CP as an SNMP agent
The CP supports data queries in the following SNMP versions:
SNMPv1 (standard)
SNMPv3 (Security)
It returns the contents of MIB objects of the standard MIB II according to RFC 1213 and the
Siemens Automation MIB.
MIB II
The CP supports the following groups of MIB objects:
System
Interfaces
The "Interfaces" MIB object provides status information about the CP interfaces.
IP
ICMP
TCP
UDP
SNMP
The following groups of the MIB II standard are not supported:
Adress Translation (AT)
EGP
Transmission
Siemens Automation MIB
The following exceptions / restrictions apply to the CP.
Write access is permitted only for the following MIB objects of the system group:
sysContact
sysLocation
sysName
A set sysName is sent as the host name using DHCP option 12 to the DHCP server to
register with a DNS server.
For all other MIB objects / MIB object groups, only read access is possible for security
reasons.
Traps are not supported by the CP.
For more detailed information about the MIB files and SNMP, refer to the manual /5/
(Page 110).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 and is the answer not in the manual?

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 Specifications

General IconGeneral
Compatible ControllersS7-1200
InterfaceEthernet
Power Supply24 V DC
Number of Possible Connections8
Mounting TypeDIN rail
Weight200 g
Data Transfer Rate10/100 Mbps
ProtocolsTCP/IP, UDP, DNP3, IEC 60870-5-104
Supply Voltage20.4 ... 28.8 V DC
Current Consumption100 mA
Operating Temperature-20 ... +60 °C