EasyManuals Logo

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 User Manual

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
Diagnostics and upkeep
5.6 Downloading firmware
CP 1243-1
Operating Instructions, 12/2016, C79000-G8976-C365-02
99
5. With a CPU version V4.0 or higher, create a user in the user management with the name
"admin".
You need to assign the right to perform firmware updates in the access level.
The procedure for establishing a connection to the Web server depends on whether you
have enabled or disabled the "Allow access only using HTTPS" option in the "General"
parameter group:
Connection establishment with HTTP
Procedure if the "Allow access only using HTTPS" option is disabled
Connection establishment with HTTPS
Procedure if the "Allow access only using HTTPS" option is enabled
These two variants are described in the following sections.
Requirement: The new firmware file is stored on your engineering station.
You will find the requirements for access to the Web server of the CPU (permitted Web
browser) and the description of the procedure in the STEP 7 information system under the
keyword "Information about the Web server".
Connection establishment with HTTP
1. Connect the PC on which the new firmware file is located to the CPU via the Ethernet
interface.
2. Enter the address of the CPU in the address box of your Web browser:
http
://<IP
address>
3. Press the Enter key.
The start page of the Web server opens.
4. Click on the "Download certificate" entry at the top right of the window.
The "Certificate" dialog opens.
5. Download the certificate to your PC by clicking the "Install certificate ..." button.
The certificate is loaded on your PC.
You will find information on downloading a certificate in the help of your Web browser and
in the STEP 7 information system under the key words "HTTPS" or "Access for HTTPS
(S7-1200)".
6. When the connection has changed to the secure mode HTTPS ("
https
://<IP address>/..."
in the address box of the Web server), you can continue as described in the next section
"Downloading firmware".
If you terminate the connection to the Web server, the next time you can log in with the
Web server without downloading the certificate using HTTP.
Connection establishment with HTTPS
1. Connect the PC on which the new firmware file is located to the CPU via the Ethernet
interface.
2. Enter the address of the CPU in the address box of your Web browser:
http
s://<IP
address>

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 and is the answer not in the manual?

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 Specifications

General IconGeneral
Compatible ControllersS7-1200
InterfaceEthernet
Power Supply24 V DC
Number of Possible Connections8
Mounting TypeDIN rail
Weight200 g
Data Transfer Rate10/100 Mbps
ProtocolsTCP/IP, UDP, DNP3, IEC 60870-5-104
Supply Voltage20.4 ... 28.8 V DC
Current Consumption100 mA
Operating Temperature-20 ... +60 °C

Related product manuals