Parameter data records
B.1 Parameter assignment and structure of the parameter data records
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
Manual, 09/2016, A5E36647959-AB
57
The description of the WRREC instruction and the error codes is available in the STEP 7
online help.
Operation of the module behind a PROFIBUS DP interface module
If the module is operated behind a PROFIBUS DP interface module, the parameter data
records 0 and 1 are not read back. You obtain the diagnostics data records 0 and 1 with the
read back parameter data records 0 and 1. You can find additional information in the
Interrupts section of the manual for the PROFIBUS DP interface module on the Internet
(http://support.automation.siemens.com/WW/view/en/78324181).
Assignment of data record and channel
The parameters in data records 0 to 9 and in data record 9 are available for 1x 9-channel
configuration and are assigned as follows:
Data record 0 for channel 0
Data record 1 for channel 1
Data record 6 for channel 6
Data record 7 for channel 7
Data record 8 for channel 8 (reference channel)
For configuration 9 x 1-channel, the module has 9 submodules with one channel each and
one submodule for the reference channel. The parameters for the channel are available in
data record 0 and are assigned as follows:
Data record 0 for channel 0 (submodule 1)
Data record 0 for channel 1 (submodule 2)
Data record 0 for channel 6 (submodule 7)
Data record 0 for channel 7 (submodule 8)
Data record 0 for channel 8 (submodule 9) or reference channel
Address the respective submodule for data record transfer.