EasyManua.ls Logo

Siemens Simatic S7-1500 - Terminal and Block Diagram of the Analog On-Board I;O

Siemens Simatic S7-1500
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Representation of analog values
C.1 Representation of input ranges
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
72 Manual, 09/2016, A5E36647959-AB
C.1
Representation of input ranges
The tables below set out the digitized representation of the input ranges separately for
bipolar and unipolar input ranges. The resolution is 16 bits.
Table C- 2 Bipolar input ranges
Dec.
value
Measured
value in %
Data word
Range
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
32767 >117.589 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Overflow
32511
117.589
0
1
1
1
1
1
1
0
1
1
1
1
1
1
1
1
Overshoot
range
27649
100.004
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
1
27648
100.000
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
0
Rated range
1
0.003617
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-1
-0.003617
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-27648
-100.000
1
0
0
1
0
1
0
0
0
0
0
0
0
0
0
0
-27649
-100.004
1
0
0
1
0
0
1
1
1
1
1
1
1
1
1
1
Undershoot
range
-32512
-117.593
1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
-32768
<-117.593
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Underflow
Table C- 3 Unipolar input ranges
Dec.
value
Measured
value in %
Data word
Range
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
32767
>117.589
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Overflow
32511
117.589
0
1
1
1
1
1
1
0
1
1
1
1
1
1
1
1
Overshoot
range
27649
100.004
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
1
27648
100.000
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
0
1
0.003617
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
Rated range
0
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-1
-0.003617
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Undershoot
range
-4864
-17.593
1
1
1
0
1
1
0
1
0
0
0
0
0
0
0
0
-32768
<-17.593
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Underflow

Other manuals for Siemens Simatic S7-1500