EasyManua.ls Logo

Siemens Simatic S7-1500

Siemens Simatic S7-1500
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Representation of analog values
C.3 Analog value representation for resistance-type transmitters / resistance thermometers
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
Manual, 09/2016, A5E36647959-AB
77
C.3.5
Thermal resistor Ni 10, 100, 120, 200, 500, 1000 GOST Standard
The following tables list the decimal and hexadecimal values (codes) of the possible
resistance thermometer ranges.
Table C- 11 Thermal resistor Ni x0 GOST Standard (0.006170)
Ni x0 GOST
Standard
in °C
(1 digit =
0.1 °C)
Units
Ni x0 GOST
Standard
in °F
(1 digit =
0.1 °F)
Units
Ni x0 GOST
Standard
in K
(1 digit =
0.1 K)
Units
Range
dec.
hex.
dec.
hex.
dec.
hex.
> 212.4
32767
7FFF
> 414.3
32767
7FFF
> 485.6
32767
7FFF
Overflow
212.4
:
180.1
2124
:
1801
084C
:
0709
414.3
:
356.1
4143
:
3561
102F
:
0DE9
486.6
:
453.3
4856
:
4533
12F8
:
11B5
Overrange
180.0
:
-60.0
1800
:
-600
0708
:
FDA8
356.0
:
-76.0
3560
:
-760
0DE8
:
FD08
453.2
:
213.2
4532
:
2132
11B4
:
854
Rated range
-60.1
:
-105.0
-601
:
-1050
FDA7
:
FBE6
-76.1
:
-157.0
-761
:
-1570
FD07
:
F9DE
213.1
:
168.2
2131
:
1682
853
:
692
Underrange
< -105.0
-32768
8000
< -157.0
-32768
8000
< 168.2
32768
8000
Underflow

Other manuals for Siemens Simatic S7-1500