EasyManua.ls Logo

Siemens Simatic S7-1500 - Analog Value Representation for Resistance-Type Transmitters; Resistance Thermometers; Resistance-Type Transmitters 150, 300, 600, 6000 Ohm; Thermal Resistor Pt 10, 50, 100, 200, 500, 1000 Standard;Gost

Siemens Simatic S7-1500
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Representation of analog values
C.3 Analog value representation for resistance-type transmitters / resistance thermometers
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
74 Manual, 09/2016, A5E36647959-AB
C.3
Analog value representation for resistance-type transmitters /
resistance thermometers
C.3.1
Resistance-type transmitters 150, 300, 600, 6000 Ohm
The following tables list the decimal and hexadecimal values (codes) of the possible
resistance-based sensor ranges.
Table C- 6 Resistance-based sensors of 150 , 300 , 600 , and 6000
Values
Resistive transmitter range
dec
hex
150
300
600
6000
32767 7FFF >176.38 >352.77 >705.53 >7055.3 Overflow
32511
7EFF
176.38
352.77
705.53
7055.3
Overshoot range
27649 6C01
27648
6C00
150
300
600
6000
Rated range
20736
5100
112.5
225
450
4500
1
1
5.43 m
10.85 m
21.70 m
217 m
0
0
0
0
0
0
C.3.2
Thermal resistor Pt 10, 50, 100, 200, 500, 1000 Standard/GOST
Thermal resistor Pt x0 Standard and Pt x0 GOST Standard
Table C- 7 Thermal resistor Pt x0 Standard (0.003851, 0.003916, 0.003902, 0.003920) and Pt x0 GOST Standard
(0.003910)
Pt x0 Stan-
dard in °C
(1 digit =
0.1°C)
Units
Pt x0 Stan-
dard in °F
(1 digit = 0.1
°F)
Units
Pt x00 Stan-
dard in K
(1 digit = 0.1
K)
Units
Range
dec
hex
dec
hex
dec
hex
> 1000.0
32767
7FFF
> 1832.0
32767
7FFF
> 1273.2
32767
7FFF
Overflow
1000.0
:
850.1
10000
:
8501
2710
:
2135
1832.0
:
1562.1
18320
:
15621
4790
:
3D05
1273.2
:
1123.3
12732
:
11233
31BC
:
2BE1
Overshoot
range
850.0
:
-200.0
8500
:
-2000
2134
:
F830
1562.0
:
-328.0
15620
:
-3280
3D04
:
F330
1123.2
:
73.2
11232
:
732
2BE0
:
2DC
Rated range
-200.1
:
-243.0
-2001
:
-2430
F82F
:
F682
-328.1
:
-405.4
-3281
:
-4054
F32F
:
F02A
73.1
:
30.2
731
:
302
2DB
:
12E
Undershoot
range
< -243.0
-32768
8000
< -405.4
-32768
8000
< 30.2
32768
8000
Underflow

Other manuals for Siemens Simatic S7-1500