Parameter data records
B.1 Parameter assignment and structure of the parameter data records
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
64 Manual, 09/2016, A5E36647959-AB
Hardware interrupt limits
The values that you can set for hardware interrupts (high/low limit) must not exceed the
over/underrange of respective rated measuring range.
The following tables list the valid hardware interrupt limits. The limit values depend on the
selected measuring type and range.
Table B- 6 Limits for voltage and resistance
Voltage
Resistor
±25 mV, ±50 mV, ±80 mV, ±250
mV, ±500 mV, ±1 V
150 Ω, 300 Ω, 600 Ω, 6 kΩ
32510 32510 High limit
-32511
1
Low limit
Table B- 7 Limits for thermocouple types B, C, E, and J
Thermocouple
Type B
Type C
Type E
Type J
°C
°F
K
°C
°F
K
°C
°F
K
°C
°F
K
2069
9
3276
5
2343
1
2499
9
3276
5
2773
1
1199
9
2191
9
1473
1
1449
9
2641
9
1723
1
High
limit
1
321
2733
-1199
-1839
1533
-2699
-4539
33
-2099
-3459
633
Low limit
Table B- 8 Limits for thermocouples type K, N, R, and S
Thermocouple
Type K
Type N
Types R, S
°C
°F
K
°C
°F
K
°C
°F
K
16219
29515
18951
15499
28219
18231
20189
32765
22921
High limit
-2699
-4539
33
-2699
-4539
33
-1699
-2739
1033
Low limit
Table B- 9 Limits for thermocouple type T and TXK
Thermocouple
Type T
Type TXK
°C
°F
K
°C
°F
K
5399
10039
8131
10499
19219
13231
High limit
-2699
-4539
33
-1999
-3279
733
Low limit