Representation of analog values
C.4 Representation of analog values for thermocouples
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
Manual, 09/2016, A5E36647959-AB
83
Table C- 24 Thermocouple type TXK/XKL GOST
Type
TXK /XKL
in °C
Values
Type
TXK /XKL
in °F
Values
Type
TXK/XKL
in K
Values
Range
dec.
hex.
dec.
hex.
dec.
hex.
> 1050.0
32767
7FFF
> 1922.0
32767
7FFF
> 1323.2
32767
7FFF
Overflow
1050.0
:
800.1
10500
:
8001
2904
:
1FA1
1922.0
:
1472.1
19220
:
14721
4B14
:
3981
1323.2
:
1073.3
13232
:
10733
33B0
:
29ED
Overrange
800.0
:
-200.0
8000
:
-2000
1F40
:
F830
1472.0
:
-328.0
14720
:
-3280
3980
:
F330
1073.2
:
73.2
10732
:
732
29EC
:
02DC
Nominal
range
< -200.0
-32768
8000
< -328.0
-32768
8000
< 73.2
-32768
8000
Underflow