CPU1517H-3PN (6ES7517-3HP00-0AB0)
Equipment Manual, 11/2022, A5E42011886-AD
10
Product overview
3
3.1 New functions
This section contains an overview of the most important new firmware functions of the CPU
compared with the predecessor version CPU (V2.9).
New functions of the CPU in firmware version V3.0
New functions Customer benefits Where can I find informa
tion?
Support
PROFINET system redundancy R1
As of FW version V3.0, the S7-1500H redund
ant system supports PROFINET system redund
ancy R1:
• ET 200SP IM 155-6 PN R1
(6ES7155-6AU00-0HM0)
• ET 200SP HA IM 155-6 PN HA
(6DL1155-6AU00-0PM0)
• ET 200iSP IM 152-1 PN
(6ES7152-1BA00-0AB0)
R1 devices are equipped with two interface
modules compared to S2 devices. If one inter
face module fails, the R1 device can still be
reached by the H-CPUs via the second inter
face module. Thus, R1 devices have a higher
availability than S2 devices.
• S7-1500R/H System Manual
(https://support.industry.
siemens.
com/cs/ww/en/view/10975
4833)
• PROFINET Function Manual
(http://support.automation.
siemens.
com/WW/view/en/4994885
6)
New configuration variants for S7-1500H As of FW version V3.0, the S7-1500H redund
ant system supports additional configuration
variants:
• Configuration of PROFINET rings with R1
devices
• Configuration of a line topology with S2
devices, switched S1 devices
• Configuration of a line topology with R1
devices
• Configuration of a combined topology with
R1 devices, S2 devices
• Configuration without additional devices
This allows you to connect the S7-1500H
redundant system to almost any network
topology and solve complex automation tasks.
S7-1500R/H System Manual
(https://support.industry.
siemens.
com/cs/ww/en/view/10975483
3)
OB 70 As of FW version V3.0, OB 70 (I/O redundancy
error) is available for the diagnostics of R1 and
S2 devices in S7-1500H systems.
S7-1500R/H System Manual
(https://support.industry.
siemens.
com/cs/ww/en/view/10975483
3)