Technology functions
3.2 Pulse generators
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
53
Setting and changing the output value (frequency)
You set the frequency with the OUTPUT_VALUE directly with the control program in the
control interface. The value is specified in the real format and the unit is always "Hz". The
possible range depends on the parameter "High-speed output (0.1 A)" as follows:
High-speed pulse output deactivated
Frequency (OUTPUT_VALUE) 0.1 Hz to 10,000 Hz
High-speed pulse output activated
Frequency (OUTPUT_VALUE) 0.1 Hz to 100,000 Hz
Standard output (100 Hz output)
Frequency (OUTPUT_VALUE) 0.1 Hz to 100,000 Hz
The new frequency is applied at the start of the next period. The new frequency has no
impact on the falling edge or the pulse-cycle ratio. However, the application can take up to
10 s depending on the previously set frequency.
Accuracy of the output frequency
The configured output frequency is output with a frequency-dependent accuracy at the digital
output PWM DQA. You can find an overview of the accuracy as a function of the frequency
used in the section Interconnection overview of outputs (Page 100).
Parameters of the frequency output mode
Category
Parameter
Meaning
Value range
Default
Reaction to
CPU STOP
Reaction to CPU
STOP
The parameter "Output substitute
value" generates a substitute
value upon CPU STOP, which you
can define with the parameter
"Substitute value for pulse output
(DQA)".
Output substitute value
Output substi-
tute value
The parameter "Continue opera-
tion" still generates the frequency
output signal upon CPU STOP,
which was generated before the
CPU STOP.
Continue operation
Substitute value
for pulse output
(DQA)
If you have set the option "Output
substitute value" for "Reaction to
CPU STOP", the parameter "Sub-
stitute value for pulse output
(DQA)" defines the substitute
value to be used for the pulse
output of the channel.
If you have set the option "Contin-
ue operation" for "Reaction to CPU
STOP", the parameter "Substitute
value for pulse output (DQA)"
cannot be selected.
0
(use substitute value 0)
0
1
(use substitute value 1)

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals