Errors and diagnostics
11.5 Operator error
Counter module FM 450-1
Manual, 02/2014, A5E03648739-02
109
11.3
Initiation of diagnostics interrupts
What is a diagnostics interrupt?
If the user program is to respond to an internal or external fault, you can set the parameters
for a diagnostic interrupt that will break off the cyclical program of the CPU device and calls
the diagnostics interrupt OB (OB 82).
Which events can initiate a diagnostic interrupt?
The following events can initiate a diagnostic interrupt:
The external auxiliary 1L+/1M voltage is faulty.
5.2 VDC encoder supply short circuited or overloaded.
The module parameters are incorrectly assigned.
Watchdog timeout
RAM defective
Hardware interrupt lost
Signal A faulty (wire breakage, short circuit, cable missing)
Signal B faulty (wire breakage, short circuit, cable missing)
Signal N faulty (wire breakage, short circuit, cable missing)
Enabling the diagnostic interrupt
You disable or enable the interrupts for the module and you choose whether the module is to
initiate a diagnostic interrupt and/or a hardware interrupt.
Responses to a diagnostic interrupt
If an event occurs that can trigger a diagnostic interrupt, the following happens:
The diagnostic information is stored in the diagnostic data records DS0 and DS1 on the
module.
An error LED lights up.
The diagnostic interrupt OB is called (OB82).
Diagnostic data record DS0 is entered in the start information of the diagnostic interrupt
OB.
The count process continues unchanged.
If no OB82 has been programmed, the CPU goes into STOP.

Table of Contents

Related product manuals