Modes, settings, parameters and commands
8.12 Initiating a process interrupt
Counter module FM 450-1
66 Manual, 02/2014, A5E03648739-02
Overview of modes, settings and commands
Which modes are available?
For the FM°450-1 there are the three following modes:
Table 8- 1 Operating modes of FM°450-1
Continuous counting
Starting from the current counter status the FM°450-1 counts
Single counting with SW gate
When the gate opens, the FM 450-1 counts from the load value to
Periodic counting with SW
When the gate opens, the FM 450-1 counts between the load value
You can configure the two FM 450-1 counters in different modes.
The default setting is the "Continuous counting" mode.
Choice of count range, behavior of the two digital outputs, pulse duration, evaluation of the
count signals, and the selection of the signal to set the counter all depend on the mode.
Which settings are available?
You can adapt the FM 450-1 to your count job by means of the following five settings:
Table 8- 2 The FM 450-1 settings
You select the count limit with the count range.
Behavior of digital outputs Q0
You can choose between six possibilities for the behavior of the
outputs on reaching the comparison value.
Pulse duration indicates the time for which the output is to be set.
Triggering hardware
When the various selectable events occur, the FM 450-1 can trigger
Encoders You must specify different settings for the encoder used. These are
described in section "Encoder signals and their evaluation