Wiring
4.4 Module status after power is switched on
Counter module FM 450-1
Manual, 02/2014, A5E03648739-02
35
4.3
Wiring Front Connectors
Cables
There are a few rules you must observe when selecting the cables:
The cables for the digital inputs must be shielded.
The cables for the count signals must be shielded.
You must apply the shields to the count signal cables both on the pulse encoder and in
close proximity to the module, e.g. via the shield application element.
Cables A and /A, B and /B, N and /N of the incremental 5-V encoder must be twisted in
pairs.
The following figure shows details relating to the connection of incremental 5-V encoders.