Wiring
4.4 Module status after power is switched on
Counter module FM 450-1
Manual, 02/2014, A5E03648739-02
31
5 V encoder RS
422, symmetrical
24-V pulse
encoder with
direction level
Digital input 1I2 (set counter)
Digital input 2I2 (set counter)
44 -
24 V load voltage for the digital inputs and outputs
Load voltage ground for digital inputs and outputs
Note
The circuits for the counter inputs (encoder power supply,
encoder signals) are isolated
electrically toward the ground of the CPU. Hence you must connect terminal 4 (1M) to the
ground of the CPU with a low impedance!
If you supply the encoders with external voltage, you must also connect the mass of this
externa
l voltage supply to the ground of the CPU.
Auxiliary voltage 1L+, 1M
To supply the 5 V and 24 V encoders with voltage, connect a 24 DC V to the 1L + and 1M
terminals.
An integrated diode protects the module from reversing the polarity of the auxiliary voltage.
The module monitors whether the auxiliary voltage is connected.