EasyManua.ls Logo

Siemens SIMATIC S7 CP340 - Page 63

Siemens SIMATIC S7 CP340
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 MODBUS RTU Protocol communication
CP340/CP341/CP440/CP441 Communication and Programming
Entry-ID: 88867653, V1.0, 02/2014
63
Siemens AG 2014 All rights reserved
Fig. 114: Distribution of MODBUS Slave addresses
6. FC01, 05, 15: status of read and forced output bit. The left side is info transfer
address, and the right side is corresponding PLC address area, viz. the left
addresses from 0 to 23 match MODBUS address area 00001 to 00024, and the
corresponding Siemens data area is M0.0-M2.7.24 to 47 match the MODBUS
Address area 00025 to 00048, and the corresponding Siemens data area is Q0.0
to Q2.7.Slave addresses 48 to 79 and 80 to 111 match the Modbus address areas
00049 to 00080 and 00081 to 00112, and the corresponding Siemens data area is
Timer, Counter. FC02 reads input data status, and the address matching is as
stated above.
Fig. 115: Distribution of MODBUS Slave addresses
7. FC03,06,16 configuration output register data area corresponds to Siemens
data area DB block.

Table of Contents

Related product manuals