Description, technical data  12.2010 
16 ENGLISH  Siemens AG    6RX1700-0DD74 
  SIMOREG DC-MASTER Converter Commutation Protector    Operating Instructions 
3  Description, Technical Data 
3.1 Description 
Application 
The SIMOREG DC-MASTER Converter Commutation Protector (SIMOREG CCP) is used to 
protect the semiconductor fuses of a line-commutated converter when operating in the inverter 
mode. When an inverter commutation fault occurs, a high current flows in the regenerative 
feedback direction via the line supply or a cross-current in the converter. SIMOREG CCP limits the 
current to a non-hazardous value so that the thyristors and the associated super-fast fuses are 
protected. This therefore eliminates the complex replacement of fuses that takes a considerable 
amount of time. Although it cannot prevent inverter commutation faults, it can provide protection 
against its effects.  
Compatibility 
The SIMOREG CCP is compatible to line-commutated SIMOREG DC-MASTER converters (from 
software release 2.2) and SINAMICS DCM (from software release 1.2).   
It can be used for converters connected in parallel. 
 
 
Note 
It is not possible to use the SIMOREG CCP for converters connected in series. 
 
Mode of operation 
The line supply voltage, line current and the armature voltage are continually sensed in the basic 
converter unit. These quantities are used to identify as to whether a commutation fault (inverter 
commutation fault) has occurred. 
If this is the case, then the following occurs: 
1.  The firing pulses are immediately disabled in the SIMOREG DC-MASTER or SINAMICS DCM. 
2.  The basic converter unit sends a turn-off command to the SIMOREG CCP (via the serial 
interface) 
3.  SIMOREG CCP turns-off the thyristors by connecting the pre-charged quenching capacitors 
anti-parallel to all thyristors. As a consequence, the current commutates from the converter into 
SIMOREG CCP. The quenching capacitors are initially discharged by the current that has been 
commutated and then they are charged. The armature current starts to decrease as soon as the 
voltage of the quenching capacitors has reached the value of the motor EMF. However, the 
armature voltage continues to increase. As soon as it has reached the limit value, resistors are 
switched-in, which absorb the energy fed back from the motor during the remaining time of the 
current reduction phase. 
4.  A fault message is output in the basic converter unit (Fault F030 or F60030). 
5.  The SIMOREG CCP re-charges the quenching capacitors with the reverse polarity so that a 
new turn-off operation is possible. 
 
 
Note 
After the line supply voltage has been connected and after a quenching operation, wait and recovery 
times must be maintained, refer to the Technical data.