12.2010 Maintenance
Siemens AG 6RX1700-0DD74 ENGLISH 67
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
8.1 Software update of the SIMOREG CCP
1
Switch-off the electronics power supply of the
SIMOREG CCP
2
Connect one COM port of the PC to connector
X300 at the SIMOREG CCP.
Order number of the cable: 6SX7005-0AB00
(also see Chapter 6.5)
3
Switch-on the electronics power supply AND
while doing this press button S1 on the Power
Interface module C98043-A7046
⇒ the SIMOREG CCP goes into the
programming mode (the yellow monitoring
LED on the SIMOREG CCP remains dark)
Note:
From this instant onwards, a timer runs in the
SIMOREG CCP for approximately 2 minutes. If,
during this time, the update is not started from the
PC, then the SIMOREG CCP returns to the
normal operating state. To restart the software -
update, the sequence from step 1 should be
repeated.
4
At the PC, start the load program
LOAD_CCP.exe and using the "Open file" button,
select the required data file (7046Axxx.hex).
Pressing the "Open" button starts the load
operation (this takes about 10 s).
Note:
In the properties dialog of a link to
LOAD_CCP.exe a parameter of form COMx can
be transferred - whereby 1 or 2 should be used
for x (default: COM1)
5
After the software has been successfully
updated, the SIMOREG CCP automatically goes
into the normal operating state (the yellow
monitoring LED at the SIMOREG CCP flashes
slowly if communication with the basic unit has
been established).
Note:
If the electronics power supply is switched-off
during the software update, then you must repeat
the operation starting from Step 4.
6
Check the new software release at 560 or
r51560[0].
7
END