Commissioning 12.2010
48 ENGLISH Siemens AG 6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
PNU
Description Value range
[dimension]
Graduation
No. of
indices
Factory
setting (FS)
Type
See/
change
(Access /
state)
U582
(2582)
Response of the commutation monitoring
[from SW 2.1 and higher]
This parameter can be used to define the response of the commutation -
monitoring.
1 After a commutation fault or an overcurrent condition has been
detected, this results in an immediate pulse cancellation and
Alarm message A030 is output. The pulses are enabled again
after approx. 20 ms and alarm message A030 disappears.
2 After a commutation fault or an overcurrent condition has been
detected, this results in an immediate pulse cancellation and
fault message F030 is output.
Notice:
The setting U582=1 is not permissible for a selected SIMOREG CCP
(P790=6)!
1 to 2
1
Ind: None
FS=2
Type: O2
P052 = 3
P051 = 40
online
U583
(2583)
Test command for the SIMOREG CCP
[from SW 2.2 and higher]
This parameter can be used to issue a turn-off command to the SIMOREG
CCP for test purposes.
0 No turn-off command is issued
1 A turn-off command is issued in MI
2 A turn-off command is issued in MII
After issuing a single turn-off command to the SIMOREG CCP, this
parameter automatically sets itself back to the value 0!
Note:
If the test command is issued while operational (i.e. in operating states I and
II), then the basic converter defines the torque direction required to select
the correct test command. In the operating state, torque direction 0 (--) the
test command is issued in torque direction I.
0 to 2
1
Ind: None
FS = 0
Type: O2
P052 = 3
P051 = 40
online
7.1.2 SINAMICS DCM parameters
(see below for a detailed description)
r50047[0..31] Faults, supplementary information
r50071 Rated unit supply voltage for armature
p50790 P2P interface operating mode
p50795 P2P/CCP bus termination
p50797 P2P interface telegram monitoring time
r50799[0..8] P2P/CCP diagnostics
r51560[0..1] CCP software version
r51569[0...15] CCP serial number
r51570 CCP order number
r51571 CCP rated supply voltage
r51572 CCP rated current
r51574.0...12 CO/BO: CCP state
r51575 CO: CCP I2t value voltage limiting chopper 1
r51576 CO: CCP I2t value voltage limiting chopper 2
p51577 CCP chopper voltage setpoint, upper response threshold
p51578 CCP quenching capacitor pre-charging voltage setpoint
r51579.0...7 CO/BO: CCP command
p51580 Commutation monitoring, control word
p51583 CCP test turn-off command