12.2010 Installation
Siemens AG 6RX1700-0DD74 ENGLISH 25
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
Remove the front cover of the SINAMICS DCM
Break-off the extension of the module A7126 Allocation Board
Using the guide slots in the holder for the electronic modules, position the Firing Unit Trigger
Board A7103 and by shifting the plug connection (X110), establish a connection to the
Allocation Board A7126
Fasten the Firing Unit Trigger Board A7103 using the screw provided, tightening torque
1 Nm
The BOP holder can be released at the side and swung upwards to route the connecting
cable
After connecting the cable (see Chapter 6.3.3) relocate the front cover of the SINAMICS DCM
and fasten using all of the screws