The grounding conductor can be connected as follows:
With stranded cables with cable lugs
With flat cables with cable end designed accordingly
Connecting the grounding conductor
Use the connecting terminals designated for the grounding conductor in the terminal box.
Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
Arrange the flat washer and spring washer under the screw head.
Check that the maximum permissible clamping thickness of 10 mm for the cable lug or strap
is not exceeded.
Fasten the clamping screw according to the following table. Screw-in depth and tightening
torque are different depending on whether cable lugs or ground terminals are used.
Screw Screw-in depth Tightening torque
M12 x 25 > 16 mm 38 Nm
M16 x 35 > 20 mm 92 Nm
Tightening torque of bolts with cable lugs
Screw Screw-in depth Tightening torque
M6 > 9 mm 8 Nm
M8 > 12 mm 20 Nm
M10 > 15 mm 40 Nm
Tightening torque of bolts with ground terminals
6.3 Inserting and routing the cables
6.3.1 Connecting the machine for a specific direction of rotation
The technical data stipulate the following with respect to the motor connection:
Direction of rotation
The number and arrangement of the terminal boxes
The circuit and connection of the motor winding
Electrical connection
6.3 Inserting and routing the cables
SIMOTICS HV C 1NA14544WA600AG0-Z
54 Operating Instructions 06/2018