EasyManua.ls Logo

Siemens SIMOTICS XP 1LA5 - Tightening Torques; Electrical Connections - Termincal Board Connections; Cable Glands

Siemens SIMOTICS XP 1LA5
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection
Explosion-protected machines
56100000002002, 01/2016
113
Frame size
Type
Type of protection /
Zone
Standard thread
Additional
thread with
mounting parts
180 1LG4
1LG6
Non sparking "n"
M 40x1.5 2 M 20x1.5 2
Zone 21
Zone 22
180
1MA6
Increased safety "e"
M 40x1.5
2
M 16x1.5
2
200 ... 225 1LA5
Zone 21
M 50x1.5 2 M 16x1.5 1
Zone 22
200
1MA6
Increased safety "e"
M 50x1.5
2
M 16x1.5
2
200 1LG4
1LG6
Non sparking "n"
M 50x1.5 2 M 20x1.5 2
Zone 21
Zone 22
225 1LG4
1LG6
1MA6
Increased safety "e"
M 50x1.5 2 M 20x1.5 2
Non sparking "n"
Zone 21
Zone 22
6.2 Tightening torques
6.2.1 Electrical connections - Termincal board connections
Table 6-3 Tightening torques for electrical connections on the terminal board
Thread ∅
M 3,5
M 4
M 5
M 6
M 8
M 10
M 12
M 16
Nm
min
0,8
0,8
1,8
2,7
5,5
9
14
27
Ma
x.
1,2 1,2 2,5 4 8 13 20 40
6.2.2 Cable glands
Note
Avoid damaging the
cable jacket.
Adapt the tightening torques to the cable jacket materials.

Table of Contents

Related product manuals