Electrical connection
Explosion-protected machines
120 56100000002002, 01/2016
Connection terminal 1MA6, 1MB153., 1MB163. and 1LG4/6 in type
of protection Ex nA.
Conductor
cross-
section
[mm²]
Frame
size/option
18. ... 22.
2,5 … 25
25. ... 28.
10 … 95
31.
25 … 135
31. + L00 / R50 50 … 300
18. ... 22.
… 16
25. ... 28.
… 35
31.
… 70
31. + L00 / R50 … 120
18. ... 22.
16 … 50
25. ... 28.
50 … 120
31.
95 … 240
31. + L00 / R50
120 … 400
6.5 Connecting converters
NOTICE
Excessively high supply voltage
Material damage can occur if the supply voltage is too high for the
insulation system.
The machines can be operated with line voltages ≤ 500 V with
SINAMICS G converters and SINAMICS S converters (uncontrolled and
controlled infeed) when maintaining the permissible peak voltages.
The maximum permissible voltage rate of rise (gradient) is 9 kV/µs.
Û
conductor-conductor
≤ 1500 V; Û
conductor-ground
≤ 1100 V
For VSD machines, the following data apply:
Û
conductor-conductor
≤ 1600 V, Û
conductor-ground
≤ 1400 V, voltage rise times of
ts > 0.1 µs.
See the list of additional operating instructions.