Installation 06.2006
6SE7087-6KP50 Siemens AG
5-2 Operating Instructions SIMOVERT MASTERDRIVES
Foreign particles
The units must be protected against the ingress of foreign particles
as otherwise their function and operational safety cannot be
ensured.
Dust, gases, vapors
Equipment rooms must be dry and dust-free. Ambient and cooling
air must not contain any electrically conductive gases, vapors and
dust which could diminish the functionality. If necessary, filters
should be used or other corrective measures taken.
Cooling air
The units must only be operated in an ambient climate in
accordance with DIN IEC 721-3-3 Class 3K3. For cooling air
temperatures of more than 45 °C (113 °F) and installation altitudes
higher than 1000 m, derating is required.
Mounting
surface
100 mm
100 mm
Cooling air
Fig. 5-1 Minimum clearances for cooling
Requirements at the
point of installation