Evaluating the safety functions according to EN ISO 13849 when using two switching devices
10.2 Evaluation of "Evaluate"
Application document for functional safety STO, SS1 (ISO 13849-1)
Compact User Manual, 09/2016, A5E34871844AM
57
10.2
Evaluation of "Evaluate"
Result
Result
Reason
PL
e
Derived from the evaluation according to IEC 62061
PFH
D
Average probability of a dangerous
failure per hour
5.42 E-09
Parameter
Component
Value
Definition
PFH
D
(basic device advanced)
3SK1121 basic device
3.7 E-09
SIEMENS AG
PFH
D
(output expansion)
3SK1211 output ex-
pansion
1.7 E-09
PFH
D
(coupling relay K
AH[n]
)
Article number
Phoenix 2981981
2.02 E-11 Phoenix Contact