Evaluating the safety functions according to EN ISO 13849 when using two switching devices
10.5 Result when using two power contactors
Application document for functional safety STO, SS1 (ISO 13849-1)
Compact User Manual, 09/2016, A5E34871844AM
61
10.5
Result when using two power contactors
PL
Average probability of a dangerous failure per hour
DETECT
e
9.06 E-10
EVALUATE e 5.42 E-09
RESPOND
e
9.06E-10
Result
Reason
PL d
The PL of all tasks of the supplementary safety function is at
least d.
Average probability of a dangerous
failure per hour
7.32E-09