Evaluating the safety functions according to EN ISO 13849 when using two switching devices
10.3 Evaluation of "Respond"
Application document for functional safety STO, SS1 (ISO 13849-1)
Compact User Manual, 09/2016, A5E34871844AM
59
Evaluation of two power contactors connected in series
Result, power contactor redundant
d The values for determination are listed in the following ta-
D
Average probability of a dangerous
failure per hour
9.06E-10
Determination of the PL power contactor
High MTTF
D
> 30 years (1,563.77 years)
direct monitoring using mirror contacts
Fulfilled It is assumed that the user has taken the necessary
4 System response: One single failure does not result in the
loss of the safety function.
Calculation of MTTF
D
power contactor
B10 value power contactor
1 * 10
6
Manufacturers data
SIEMENS AG
Percentage of dangerous failures
EMERGENCY STOP command device
0.73 (73 %) Manufacturers data
op
average operating time in days per year
365 days per year
Assumption:
The device can be actuated every
day of the year
User
average operating time in hours per day
average time between the start of two con-
secutive cycles of the component
24 hours per cycle Assumption:
there is one day between actuating
the EMERGENCY STOP (testing