Evaluation of the safety function according to EN 62061
11.3 Evaluation of "Respond"
Application document for functional safety STO, SS1 (ISO 13849-1)
Compact User Manual, 09/2016, A5E34871844AM
67
Evaluation of two power contactors
Hardware fault tolerance HFT=1
D
7.3 E-09 2-channel architecture, switch off of different voltage
sources
Values to calculate the PFH
D
B10 value power contactor
1 *10
6
Manufacturers data SIEMENS AG
Percentage of dangerous
failures
0.73 (73 %) Manufacturers data
175200 h Expected service life, 20 years
C
Number of times that the
power contactor is ener-
1 / 24 h Annahme:
The device is energized once a day
The device can be energized every day of the
Diagnostic test interval
24 h It is actuated once a day.
A defective contact is detected.
susceptibility to common-
0.1 (10 %) When installed according to EN 62061, this can
assumed to be a "conservative value"
Diagnostic Coverage
0.99 (99 %) Direct monitoring using mirror contacts
Result "Respond" when using two 3WL circuit breakers
2
The tables with the values to be determined are listed in
Section 11.3.1.1.
D
Average probability of a dangerous