Installing
3.2 Overview of the interfaces
CU230P-2 Control Units
Compact Operating Instructions, 01/2017, A5E38815802B AA
11
Table 3- 2 Permissible cables and wiring options
Solid or flexible conductors Finely stranded conductor with
non-insulated end sleeve
Finely stranded conductor with
partially insulated end sleeve
Cables with twin end sleeves are not permissible.
Measures to ensure EMC-compliant wiring of the Control Unit:
● Use the shield connection kit of the Control Unit to connect the shield and provide strain
relief for cables/conductors.
Shield connection kit 1 for the CU230P-2 Control Units with all fieldbus
interfaces except for PROFINET.
6SL3264-1EA00-0FA0
Shield connection kit 3 for the CU230P-2 and CU240E-2 Control Units
with PROFINET interface.
6SL3264-1EA00-0HB0
● If you use shielded cables, then you must connect the shield to the mounting plate of the
control cabinet or with the shield support of the inverter through a good electrical
connection and a large surface area.
Additional information about EMC-compliant wiring is available on the Internet:
EMC installation guideline (http://support.automation.siemens.com/WW/view/en/60612658)
Interfaces at the lower side of the CU230P-2 Control Unit