Commissioning
4.2 Commissioning with BOP-2 operator panel
CU230P-2 Control Units
34 Compact Operating Instructions, 01/2017, A5E38815802B AA
4.2
Commissioning with BOP-2 operator panel
4.2.1
Start quick commissioning and select the application class
Starting quick commissioning
Preconditions
The power supply is switched on.
The operator panel displays setpoints and actual values.
Procedure
Proceed as follows to carry out quick commissioning:
Press the ESC key.
Press one of the arrow keys until the BOP-2 displays the "SETUP" menu.
To start quick commissioning, in the "SETUP" menu, press the OK key.
If you wish to restore all of the parameters to the factory setting before the quick
commissioning, proceed as follows:
1. Press the OK key.
2. Switchover the display using an arrow key: nO YES
3. Press the OK key.
You must select the application class if you are not using a PM230, but instead, a PM240-2,
PM240P-2 or PM330 Power Module. The next steps after having selected an application
class are described in the operating instructions.
Overview of the manuals (Page 49)
Select the motor standard.
KW 50HZ: IEC
HP 60HZ: NEMA
KW 60HZ: IEC 60 Hz
Set the inverter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
INDUCT: Third-party induction motor
1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors