Commissioning
4.2 Commissioning with BOP-2 operator panel
CU230P-2 Control Units
Compact Operating Instructions, 01/2017, A5E38815802B AA
35
Motors with motor code stamped on the rating plate:
● 1LE1 IND 100: 1LE1 . 9
● 1PC1 IND: 1PC1
● 1PH8 IND: Induction motor
● 1FP1: Reluctance motor
Depending on the inverter, the motor list in BOP-2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
inverter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor
data from p0304 and higher from the rating plate.
87 Hz motor operation The BOP-2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = KW 50HZ).
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Motor cooling:
● SELF: Natural cooling
● FORCED: Forced-air cooling
● LIQUID: Liquid cooling
● NO FAN: Without fan
Select the appropriate application:
● VEC STD: In all applications, which do not fit the other setting options.
● PUMP FAN: Applications involving pumps and fans
● SLVC 0HZ: Applications with short ramp-up and ramp-down times. However, this setting
is not suitable for hoisting gear and cranes/lifting gear.
● PUMP 0HZ: Setting only for steady-state operation with slow speed changes. We
recommend setting VEC STD if load surges in operation cannot be ruled out.
The selection option depends on the Power Module being used. There is no selection option
for PM230 Power Modules.