Technical specifications
6.2 Specific technical data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
71
Table 6- 2 PM330 frame sizes GX, 3-phase 380480 VAC
Article no.
6SL3310-
1PE33-0AA0
1PE33-7AA0
1PE34-6AA0
Rated input current
- at 380/400 V, 40° C
- at 480 V, 40° C
- at 380/400 V, 50° C
- at 480 V, 50° C
317 A
262 A
269 A
220 A
375 A
314 A
319 A
266 A
469 A
376 A
399 A
319 A
Rated input current DCP/DCN
(for 2/3 of the converter power)
- at 510 V
DC
, 40 °C
- at 650 V
DC
, 40 °C
- at 510 V
DC
, 50 °C
- at 650 V
DC
, 50 °C
255 A
209 A
217 A
177 A
315 A
263 A
268 A
223 A
392 A
314 A
333 A
267 A
Rated output current I
N
- at 380/400 V, 40° C
- at 480 V, 40° C
- at 380/400 V, 50° C
- at 480 V, 50° C
300 A
245 A
255 A
208 A
370 A
308 A
315 A
262 A
460 A
369 A
391 A
313 A
LO base load power
LO base load input current at 400 V
LO base load output current at 400 V
160 kW
307 A
290 A
200 kW
365 A
360 A
250 kW
459 A
450 A
HO base load power
HO base load input current at 400 V
HO base load output current at 400 V
132 kW
254 A
240 A
160 kW
300 A
296 A
200 kW
375 A
368 A
Fuse according to IEC
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1333-2
(450 A/690 V)
Siemens AG
≤ 100 kA
> 3.5 kA
3NE1334-2
(500 A/690 V)
Siemens AG
≤ 100 kA
> 4.5 kA
3NE1435-2
(560 A/690 V)
Siemens AG
≤ 100 kA
> 7.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1333-2
(450 A/690 V)
Siemens AG
≤ 100 kA
> 3.5 kA
3NE1334-2
(500 A/690 V)
Siemens AG
≤ 100 kA
> 4.5 kA
3NE1435-2
(560 A/690 V)
Siemens AG
≤ 100 kA
> 7.0 kA
max. power loss, at I
N
, 40 °C, 400 V
3.642 kW
4.414 kW
5.125 kW
Required cooling air flow
210 l/s
210 l/s
210 l/s
Maximum connectable cross-section of the line,
motor and DC-link cable
2 x 240 mm
2
2 x 500 kcmil
2 x 240 mm
2
2 x 500 kcmil
2 x 240 mm
2
2 x 500 kcmil
Recommended cable cross-section for 380 V/400 V
- line cable
- motor cable
2 x 120 mm
2
2 x 95 mm²
2 x 120 mm
2
2 x 95 mm²
2 x 185 mm
2
2 x 150 mm²
Recommended cable cross-section for 480 V
- line cable
- motor cable
2 x 95 mm
2
2 x 70 mm²
2 x 120 mm
2
2 x 95 mm²
2 x 120 mm
2
2 x 120 mm²
Recommended cable cross-section for 380 V/400 V
- DC link infeed (2/3 converter power)
- Braking Module
3)
2 x 120 mm
2
35 mm²
2 x 120 mm
2
35 mm²
2 x 150 mm
2
35 mm²
Recommended cable cross-section for 480 V
- DC link infeed (2/3 converter power)
- Braking Module
3)
2 x 95 mm
2
35 mm²
2 x 95 mm
2
35 mm²
2 x 120 mm
2
35 mm²

Table of Contents