Default setting 105: "Fan pressure control + ESM with fixed setpoint"
3UHVVXUHVHQVRU99ฬ
212))
(VVHQWLDOVHUYLFHPRGHVSHHGVHWSRLQW
6SHHGDFWXDOYDOXH
&XUUHQWDFWXDOYDOXH
$ODUP
)DXOW
2SHUDWLRQ
7HFKQRORJ\FRQWUROOHU
6SHHGVHWSRLQW
)L[HGYDOXH
)L[HGVSHHGVHWSRLQW
$,
',
',


$2
$2

'2



'2



'2

3
DO 0: p0730, …,
DO 2: p0732
AO 0: p0771[0], AO 1: p0771[1] DI 0: r0722.0, DI 1: r0722.1 AI 0: r0755[0]
Additional settings:
Pressure control using the technology controller
Analog inputs smoothing time constant: p0753 = 500 ms
Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
Fixed speed setpoint 15 for essential service mode (ESM): p1015 = 1350 rpm
Default setting of the technology controller:
Enable: p2200 = 1
Fixed value 1: p2201 = 40 %
Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
Ramp-up/down time for controller output: p2293 = 30 s
Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
Actual value filter time constant: p2265 = 10 s
Proportional gain K
P
, integral time T
I
, differentiation time constant T
D
: p2280 (K
P
) = 1.1,
p2285 (T
I
) = 35 s, p2274 (T
D
) = 0 s
Technology controller minimum limiting p2292 = 20 %
Technology controller output signal start value p2302 = 50 %
"Flying restart" is enabled: p1200 = 1
Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26
Designation in the BOP-2: P_F Pc5
Installing
4.5 Connecting the interfaces for the inverter control
Converter with the CU230P-2 Control Units
124 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE