Table 10-31 PM330, frame size HX, 3-phase 380 … 480 VAC
Article No. 6SL3310- 1PE35-8AA0 1PE36-6AA0 1PE37-4AA0
Rated input current
- at 380/400 V, 45° C
- at 480 V, 45° C
- at 380/400 V, 55° C
- at 480 V, 55° C
597 A
497 A
507 A
422 A
668 A
536 A
568 A
456 A
750 A
614 A
637 A
522 A
Rated input current DCP/DCN
(for 2/3 of the inverter power)
- at 510 V
DC
, 45 °C
- at 650 V
DC
, 45 °C
- at 510 V
DC
, 55 °C
- at 650 V
DC
, 55 °C
498 A
415 A
423 A
352 A
558 A
448 A
474 A
381 A
626 A
513 A
532 A
436 A
Rated output current I
N
- at 380/400 V, 45° C
- at 480 V, 45° C
- at 380/400 V, 55° C
- at 480 V, 55° C
585 A
487 A
497 A
414 A
655 A
526 A
557 A
447 A
735 A
602 A
625 A
512 A
LO base load power
LO base load input current at 400 V
LO base load output current at 400 V
315 kW
581 A
570 A
355 kW
653 A
640 A
400 kW
734 A
720 A
HO base load power
HO base load input current at 400 V
HO base load output current at 400 V
250 kW
477 A
468 A
250 kW
501 A
491 A
315 kW
562 A
551 A
Fuse according to IEC
manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
> 10.0 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
> 11.0 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
> 13.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
> 10.0 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
> 11.0 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
> 13.0 kA
max. power loss, at I
N
, 45 °C, 400 V 6.791 kW 7.687 kW 8.385 kW
Required cooling air flow 360 l/s 360 l/s 360 l/s
Maximum connectable cross-section of the line, mo‐
tor and DC-link cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 380 V/400 V
- line cable
- motor cable
2 x 240 mm
2
2 x 185 mm²
3 x 150 mm
2
2 x 240 mm²
3 x 185 mm
2
2 x 240 mm²
Recommended cable cross-section for 480 V
- line cable
- motor cable
2 x 185 mm
2
2 x 150 mm²
2 x 240 mm
2
2 x 185 mm²
2 x 240 mm
2
2 x 240 mm²
Recommended cable cross-section for 380 V/400 V
- DC link infeed (2/3 inverter power)
- Braking Module
3)
2 x 185 mm
2
35 mm²
2 x 240 mm
2
35 mm²
3 x 150 mm
2
35 mm²
Recommended cable cross-section for 480 V
- DC link infeed (2/3 inverter power)
- Braking Module
3)
2 x 150 mm
2
35 mm²
2 x 185 mm
2
35 mm²
2 x 240 mm
2
35 mm²
Technical data
10.5 Technical data, PM330 Power Module
Converter with the CU230P-2 Control Units
468 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Table of Contents

Other manuals for Siemens SINAMICS G120P