Current derating depending on the installation altitude
The permissible inverter output current is reduced above an installation altitude of 1000 m.
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@







Figure 10-9 Characteristic for the PM230 Power Module
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@





Figure 10-10 Characteristic for the PM330 GX Power Module
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@




Figure 10-11 Characteristic for the PM330 HX and JX Power Modules
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@





Figure 10-12 Characteristic for the PM250 Power Module
Technical data
10.9 Restrictions for special ambient conditions
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 513