Table 4-10 Drilling dimensions, cooling clearances and fixing
Frame
size
Drilling dimensions [mm] Cooling air clearances [mm]
1)
Fixing/torque [Nm]
h b c Top Bottom Front
FSD 430 170 7 300 350 100 4 x M5 / 6.0
FSE 509 230 8.5 300 350 100 4 x M6 / 10
FSF 680 270 13 300 350 100 4 x M8 / 25
1)
The Power Module is designed for mounting without any lateral cooling air clearance. For tolerance
reasons, we recommend a lateral clearance of approx. 1 mm.
Installing
4.3 Installing Power Modules
Converter with the CU230P-2 Control Units
72 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE