Removing a sensor
To remove a sensor, proceed as follows:
1. Loosen the screw in the sensor cover .
2. Pull out the connector.
Figure 9-12 Replacing the water sensors
3. For the temperature sensor, loosen the two screws in the sensor cover .
4. Remove the cables connected to the sensor.
5. Unscrew the sensor from the screw connection in the water pipe.
Installing a sensor
To install a sensor, proceed as follows:
1. Screw the sensor into the screw connection in the water pipe.
2. Attach the connector to the sensor.
3. Fasten the screws in the sensor cover .
4. For the temperature sensor, attach the cables directly to the sensor.
5. Lock the sensor by using the two screws to screw the cover to the sensor.
Note
Ventilating the deionized water circuit
Vent the deionized water circuit after replacing a water sensor.
Maintenance
9.7 Repair
SINAMICS SH150 6SL3805
112 Operating Instructions 05/2020