Shield connection
Do not use cable shields to conduct current. It is not permissible that the cable shield is used
as neutral or PE conductor.
Apply the cable shield so that it covers the greatest possible surface area. Use ground
clamps, ground terminals or ground screw connections.
Avoid extending the cable shield to the grounding point using a wire. This reduces the shield
effectiveness by up to 90%.
Electrical connection
6.2 Electromagnetic compatibility
SINAMICS SH150 6SL3805
68 Operating Instructions 05/2020