4 Installation and Startup
4.2 Startup (JOG from drive side)
Speed control with SINAMICS V90 and S7-300 via Profinet
Entry-ID: 109743898, V1.0, 07/2016
16
Siemens AG 2016 All rights reserved
4.2 Startup (JOG from drive side)
Table 4-1
Nr.
Action
Remarks
1.
Set drive parameter p29108 to be 1.
JOG function is enabled when p29108=1
2.
Switch to JOG menu with drive BOP operation.
3.
Press or button to run the motor.
4.3 Startup (PROFINET communication)
Table 4-2
Nr.
Action
Remarks
1.
Set drive parameter p922 to be 1.
Select standard telegram 1
2.
Make device & network configurations in the
TIA Portal:
Device name
IP address
Telegram
As shown in section 3.2.3
3.
Go online to test the PROFINET
communication.
4.
Download configurations into controller and
device if the communication works.