3 Basics
3.2 Basic parameter configuration regarding SINAMICS V90 PN
Speed control with SINAMICS V90 and S7-300 via Profinet
Entry-ID: 109743898, V1.0, 07/2016
9
Siemens AG 2016 All rights reserved
3.2.2 Configure ramp-function generator via SINAMICS V-ASSISTANT
The configuration of ramp-function generator should be configured via the
SINAMICS V-ASSISTANT.
The ramp-function generator can be configured with the Parameterize menu field of
SINAMICS V-ASSISTANT.
At the tab “Set parameter setpoint”, you can choose to activate the ramp-function
generator or deactivate it:
NOTE
You can choose to use the basic ramp-function generator or extended ramp-
function generator:
Table 3-2: Ramp-function generator relevant parameters
Par. No.
Description
Set value
P1115
Ramp-function generator selection
0
P1120
Ramp-up time
10 s
P1121
Ramp-down time
10 s
P1130
Initial rounding-off time
0 s
P1131
Final rounding-off time
0 s