3 Basics
3.2 Basic parameter configuration regarding SINAMICS V90 PN
Speed control with SINAMICS V90 and S7-300 via Profinet
Entry-ID: 109743898, V1.0, 07/2016
8
Siemens AG 2016 All rights reserved
Network:
Note: the configurations must be saved for activation.
Active configure: The active PROFINET settings can be checked from
the tab.
Table 3-1: PROFINET relevant parameters
Par. No.
Description
Set value
P922
Telegram selection
1
P8921
PN IP address. There are four
indexes. Each index maps to a
segment of the IP address.
Note: after successful
configuration, the values will be
changed to 0 automatically.
Example IP address:
192.168.0.2
P8921[0]=192
P8921[1]=168
P8921[2]=0
P8921[3]=2
P8923
PN Subnet Mask of Station. There
are four indexes. Each index maps
to a segment of the subnet mask.
Note: after successful
configuration, the values will be
changed to 0 automatically.
Example Subnet mask:
255.255.255.0
P8923[0]=255
P8923[1]=255
P8923[2]=255
P8923[3]=0
P8925
PN interface configuration
Note: after successful
configuration, the values will be
changed to 0 automatically.
2
Note: after setting p8921 and
p8923, p8925 should be set to
be 2 for activating the PN
communication.
r8931
PN IP address of station active
r8932
PN default gateway of station active
r8933
PN MAC address of station