2nd shunt release 3AX1101-..
The 2nd shunt release (-Y2) is installed whenever more than one shunt release is
needed.
In this version, the electrical “open” command is passed by means of a magnet ar-
mature to the “OPEN” latch by release of an energy storage mechanism, thus open-
ing the vacuum circuit-breaker. This opening solenoid is not designed for continuous
operation.
Shunt releases are protected against overvoltage 60 V.
Power consumption 10 W / VA
Fig. 32 2nd shunt release (51.2) Fig. 33 2nd shunt release (51.2)