Installation
52 9229 0025 176 0E
2021-11-15
Removing the transport block from the undervoltage release
Undervoltage release (-Y7)
available?
The vacuum circuit-breaker with an undervoltage release (-Y7) 3AX1103-.. is sup-
plied with a transport block.
Remove the cover (see “Removing and mounting covers” page 40).
Shift the retaining screw of the striker pin from position A to B (see the reference
note in the operating mechanism of the vacuum circuit-breaker).
Turn the locking plate by 180° and cover the thread in position A.
Screw in the retaining screw in position B.
Mount the cover again in reverse order (see “Removing and mounting covers”
page 40).
Fig. 77 As-delivered condition retaining screw in po-
sition A
Fig. 78 Remove the transport block