Installation
9229 0025 176 0E 59
2021-11-15
Tightening torques for greased threads:
- M12: 40 ±4 Nm
- M16: 100 ±10 Nm
If insulating shells are used on the system side, the main current conductors may
only have a maximum diameter or cross-section of 60 mm.
Position the insulating shell in front of the pole shell and snap it into the guides.
If necessary, snap the hooks into place by hand.
Observe the alignment of the contact system. The contact fingers must point to
the system side.
Grease the inside of the contact system with Molykote Longterm 2.
For the installation of the 1250 A contact system on the contact arm, a
Fig. 94 Installation of the insulating shell Fig. 95 Mounted insulating shell
0102-14
46
47
0102-18
Fig. 96 Installation of the 1250 A contact system with
installation aid
Fig. 97 Installation of the 1250 A contact system with
installation aid
0102-19
1.
2.
0102-20
3.
4.