Installation
60 9229 0025 176 0E
2021-11-15
3AX1445-1A mounting cone can optionally be used.
Place the assembly cone flush on the face of the contact arm (see 2.).
Push the contact system over the assembly cone until the lower part of the con-
tact fingers is in the groove (see 3.).
Completely pull out the assembly cone through the contact system (see 4.).
Grease contact fingers with Molykote Longterm 2
Mounting 2 000 A third-party contacts
Grease the screw-in area of the threaded rods with Vaseline.
Screw in the threaded rods and observe the screw-in depths (see Table “Screw-
in depths for screws or threaded rods from the contact surface in the upper and
lower connection”, on page 54).
Tightening torques apply to greased threads only
-M12: 40 ±4Nm
- M16: 100 ±10 Nm
Fig. 98 Clean thread and mount for 2 000 A contact
arms
M12: 40 ±4 Nm
M16: 100 ±10 Nm