CFC
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
T
Chart
 = 5 ∙ n
Inp
 + 5 ∙ n
Outp
 + T
TLev
 + ∑
i
 T
int
 + ∑
j
 T
Block
where:
n
Inp
Number of indications routed as input in the CFC chart
n
Outp
Number of indications routed as output in the CFC chart
T
TLev
101 Ticks in Fast Event-Triggered level
104 Ticks in Event-Triggered level
54 Ticks in Measurement level
74 Ticks in Interlocking level
T
int
Number of internal connections between 2 CFC blocks in one chart
T
Block
Used ticks per CFC block (see Table 12-4)
Table 12-4 Ticks of the Individual CFC Blocks
Element Ticks
ABS_D 2.3
ABS_R 1.5
ACOS_R 6.9
ADD_D4 3.4
ADD_R4 3.3
ADD_XMV 6.4
ALARM 1.8
AND_SPS 1.1
AND10 2.9
APC_DEF 1.2
APC_EXE 1.0
APC_INFO 3.9
ASIN_R 1.3
ATAN_R 1.2
BLINK 1.3
BOOL_CNT 2.0
BOOL_INT 1.5
BSC_DEF 1.3
BSC_EXE 1.1
BSC_INFO 2.7
BUILD_ACD 2.9
BUILD_ACT 2.2
BUILD_BSC 1.2
BUILD_CMV 2.3
BUILD_DEL 2.1
BUILD_DPS 1.4
BUILD_ENS 1.3
BUILD_INS 0.5
BUILD_Q 0.8
BUILD_SPS 0.6