Setting Values
Pickup value -50 °C to 250 °C
-58 °F to 482 °F
Increments of 1°C
Increments of 1°F
Time delay 0 s to 60 s
or ∞
Increments of 1 s
Dropout
Dropout differential 3 °C or 6 °F
Tolerances
Tripping delay ±1 % of the setting value or ±10 ms
Measured temperature value ±0.5 % of the setting value or ±1 °C or ±2 °F
12.25
Technical Data
12.25 Temperature Supervision
SIPROTEC 5, Merging Unit 6MU85, Manual 861
C53000-G5040-C074-1, Edition 01.2020